Gas Turbine 15 Mega Watt Heavy Fuel Oil Power

Gas Turbine Engines(3 UNITS)

•Rated output 4000kW
• Voltage 6600v
• Frequency 50Hz
• gas turbine MIT-26
• Generator TAKL-SCKE
• Serial number:
• Manufacturing date 2018-3
• Current 438A
• Number of phases 3 φ
• Height 3800 × width 3500 × depth 8500

Kawasaki Heavy Industries, Ltd
• Model MIT-26
• Rated output 4347 KW 40 ° C
• Rotational speed 22000/1500 min-1
• Serial number:
• Month of production 2018-2
• Kawasaki Heavy Industries, Ltd.

Hitachi
• Decelerator
• Model MPG160-23
• Reduction ratio 14.618
• Transmission power 4800KW
• Output rotational speed 1500 min-1
• Serial number:
• Manufacturing date 2018/2
• T5000A-BER

Toshiba Emergency Synchronous Generators
3 units
• Phase number 3
• Number of poles 4
• Voltage 6600V
• Power factor 0.8
• Rated continuous
Phase number 3
• Number of poles 4
• Voltage 6600V
• Power factor 0.8
• Rated continuous
• Output 5000KVA
• Current 438A
• Field voltage 70V
• Annual operation time 1000 hours
• Rotation speed 1500 min-1
• Frequency 50Hz
• Field current 455A
• Output 5000KVA
• Current 438A
• Field voltage 70V
• Annual operation time 1000 hours
• Rotation speed 1500 min-1
• Frequency 50Hz
• Field current 455A

•Refrigerant temperature 40 ° C
• Field winding 155 (F)
• Heat resistant class; Armature winding 155 (F)
• AC exciter: Output 39 KVA
• Voltage 55V
• Current 410A
• Field voltage 90V
• Protection method IP20
• Cooling method ICO 1
• Mass 9660 Kg
• Serial number:
• Standard JEC-2130-2016

Transformers (2 Units)
• Load tap switching transformer
• Standard JEC-220-2014
• Phase number 3
• Rated frequency 50Hz
• Cooling method ONAN / ONAF
• Rated Capacity (KVA) Primary 20000/22000 Secondary 20000/22000
• Rated voltage (V) primary 66000 secondary 6600
• Rated current (A) primary 175/192 secondary 1750/1925
• Test voltage value (KV) primary L1 350 AC 140 secondary L1 60 AC22
• Temperature rise limit
• Number of turns 65K Oil 60K
• 23T each in weight

More Information On The HFO Plant
Power generator

• The power generator consists of a gas turbine, AC generator, and auxiliary equipment necessary for operation. It shall be mounted on a common base and housed inside an outer case.

• The outer box has a door attached with HINGE and shall be lockable.

• The numbers indicate per unit

(1) format T5000ABER(PU5000B-ER)

(2) Exhaust system Single exhaust system

(3) Construction

• In the outside box The main equipment to be installed is as follows
• 1. Gas turbine (including reduction gear) 3 units
• 2. Alternator 3unit
• 3.Starter motors
• 4.Fuel supply system
• 5.Lubricant oil supply device

(4)Coupling method

• The gas turbine main shaft is coupled with the generator through the reduction gear and the coupling

(5) Startup method DC motor start powered by storage battery

(6) Speed characteristics Isochronous control

• Constant speed fluctuation rate ±0.3% At constant load Within
• Instantaneous speed fluctuation rate ±5% Full load on / off

• (7) Fuel consumption 1750L/h (+5%Margin)

• (8) Start time Within 40 seconds

• (9) Load input capacity 100%

• (10) Restart time Within 40 seconds by restart command after stop command

More Information On The HFO Plant

The key points of the gas turbine that drives the generator are as follows.
(1)format Simple release cycle 1 axis type
(2)Construction Consists of a centrifugal two-stage compressor, an axial flow four-stage turbine, a single-tube can combustor and a reduction gear
(3)Output 4,347kw(40℃)
(4)Rotational speed Turbine main shaft 22,000min⁻1 Output axis 1,500min⁻1
(5)Reduction gear Planetary + Parallel gear reducer
(6)Starter motor Electric type
(7)Fuel controller Electric type A heavy oil No. 1 (JIS K 2205)
(8)Fuel used Oil type: Synthetic base oil (AERO SHELL ASTO-500)
(9)Used lubricating oil Oil amount: 240L